DC-DC Converters |
Heavy Duty 48VDC input Battery Charger 288
Watts
|
Heavy Duty 48VDC input Battery Charger 576
Watts
|
Heavy Duty 48VDC input Battery Charger 1152
Watts
|
Part Number and Price |
PBCD315-48-48 $954
Allow up to 10 weeks lead time |
PBCD615-48-48
$1319
Allow up to 10 weeks lead time |
PBCD1015-48-48
$1716
Allow up to 10 weeks lead time |
Country of Origin |
Canada,
NAFTA eligible |
Nominal Input Voltage |
48VDC |
Input Voltage Range |
40VDC
to 60VDC |
Absorption Voltage |
57.60V |
57.60V |
57.60V |
Float Voltage |
54.40V |
54.40V |
54.40VDC |
Output Voltage Adjustment |
±1V typical |
Max Output Current(s) |
5 Amps |
10 Amps |
20 Amps |
Transition current |
0.75 Amps |
1.5 Amps |
3 Amps |
Duty Cycle |
100%
rated power 24 hours a day |
Reverse Polarity Protection? |
Yes |
Yes |
Yes |
Current Limiting? |
Yes |
Yes |
Yes |
Over Temperature shutdown? |
Yes |
Yes |
Yes |
Short Circuit Protection? |
Yes |
Yes |
Yes |
Stages |
2 or 3
user selectable |
Input Under voltage Shutdown? |
Yes |
Yes |
Yes |
Output Overvoltage Crowbar? |
Yes |
Yes |
Yes |
Output Crowbar Trigger
Voltage |
63.9V
± 2 Volts |
Dry Contact Output Fail
Relay? |
Yes |
Can be left Permanently
Attached? |
Yes |
Yes |
Yes |
Temperature Compensated
Charging? |
Yes |
Yes |
Yes |
Temperature Compensation
Schedule |
-120mV/°C |
Operating Temperature Range |
-25°C to +40°C |
Operating Temperature Range with
Derating |
-25°C to +50°C |
Derating |
2.5%
per °C up to +50°C |
Efficiency at maximum output |
>75 % |
>75 % |
>80 % |
Line Regulation |
<±0.5% |
Load Regulation |
<±0.5% |
Output ripple noise |
<25 mV rms |
<25 mV rms |
<50 mV rms |
Transient Response |
<2V
for 50% surge |
Switching frequency |
60
kHz |
Isolation |
Fully
isolated: >1500 volts isolation from case to any input terminal,
>500V isolation between case and any output terminal, >1500 Volts
isolation input to output. Transient voltage suppression. |
Indicators |
Audio
and visual indicators for constant current, low input voltage, low output
voltage, over temperature. Dry Contact output failure relay. |
Output Fuse |
10A AGC |
ATC 25 |
20 x 2 ATC |
Input Fuse |
15A MDA |
3A MDA |
10A MDA |
Input Connection |
cable |
cable |
cable |
Output Connections |
4
contact screw terminal |
Protection |
Over Voltage , Over current, Short Circuit , Reverse
Polarity , Over Load Over Voltage , Over
Current, Short Circuit , Reverse Polarity , Over Load |
Dimensions |
244
x 208 x 64 mm (9.6 x 8.2 x 3.5 inches) |
368
x 251 x 110 mm (9.6 x 8.2 x 3.5 inches) |
368
x 251 x 127 mm (14.5 x 9.9 x 5 inches) |
Weight |
3.4
Kg (7.5 lbs) |
3.4
Kg (7.6 lbs) |
5.5
Kg (12 lbs) |
Audible Noise |
None |
None |
None |
Typical service life |
87000 hours |
87000 hours |
87000 hours |
Warranty |
5 years |
5 years |
5 years |
Approvals |
UL458 & CSA
22.2.107.1 Pending |
UL458 & CSA
22.2.107.1 Pending |
UL458 & CSA
22.2.107.1 Pending |